top of page

BALANCING VALVES

Balancing Valves - Static

Hattersley’s range of static balancing valves includes Double Regulating Valves and Fixed Orifice Double Regulating Valves. The integral fixed orifice design offers greater accuracy than variable orifice design valves, makes set-up easier and involves fewer connections resulting in lower installation costs. Available in medium and low flow versions, Hattersley’s static balancing valves offer positive flow control at all handwheel settings.

Balancing-Valves.jpg
PREFERRED_ARRANGEMENT_BALANCING_VALVES.jpg

ONE VALVE SYSTEM (MEASUREMENT AND REGULATION AT ONE POINT)

Commissioning Set Components

ONE VALVE SYSTEM_BALANCING VALVES.jpg

VARIABLE ORIFICE DOUBLE REGULATING VALVES

VARIABLE ORIFICE DOUBLE REGULATING VALVES_ BALANCING VALVES.jpg

Fig. 631

Standard Pressure Test Points (max 120°C)

Test Probes.jpg

BS 7350

When fitted to measuring devices and strainers, test points are supplied with cap retainers in red and blue for upstream and downstream port identification. This meets the requirements of BS 7350.

Test Probes

The application of a silicone lubricant to the probe shaft prior to insertion is recommended. Hattersley Figure 631 test points are WRAS Approved products and are listed in the water fittings and materials directory.

Fig. 631  Standard Pressure Test Points (max 120°C).jpg

Fig. 1000

DZR Brass Metering Stations

Fig. 1000  DZR Brass Metering Stations.jpg

FEATURES & BENEFITS

• Precise and accurate measurement, conforming to BS 7350:1990

• Dezincification resistant material preventing corrosion cracking and fungal growth

• Flow Measurement Device is suitable for systems where pipes have been sized on the basis that pipe frictional losses lie in the range 100 to 400 Pa/m

• WRAS Approved for use with potable water up to 85°C

• Supplied with red and blue test points for upstream and downstream port identification

• Flow measurement accuracy of ±5%

DIMENSIONAL DRAWING

Fig. 1000  DZR _ Dimensional Drawing.jpg

Fig. 1000L & 1000M

DZR Brass Low & Medium Flow Metering Stations

Fig. 1000L & 1000M  DZR Brass Low & Medium Flow Metering Stations.jpg

FEATURES & BENEFITS

• Precise and accurate measurement, conforming to BS 7350:1990

• Dezincification resistant material preventing corrosion cracking and fungal growth

• WRAS Approved for use with potable water up to 85°C

• Supplied with red and blue test points for upstream and downstream port identification

• Flow measurement accuracy of ±5%

DIMENSIONAL DRAWING

Fig. 1000L & 1000M  DZR _ Dimensional Drawing.jpg

Fig. 1432, 1432L, 1432C, 1432LC

Bronze Double Regulating Valve

Fig. 1432, 1432L, 1432C, 1432LC  Bronze Double Regulating Valve.jpg

FEATURES & BENEFITS

• Provides precise and accurate flow regulation

• Easy to operate with handwheel and numerical indicator

• Robust bronze body for long service life

• WRAS Approved for use with potable water to 85°C.

• Positive flow control at all handwheel settings

DIMENSIONAL DRAWING

Fig. 1432, 1432L, 1432C, 1432LC _ Dimensional Drawing.jpg

Fig. 1732, 1732M, 1732L, 1732C, 1732MC, 1732LC

Bronze Fixed Orifice Double Regulating Valve (FODRV)

Fig. 1732, 1732M, 1732L, 1732C, 1732MC, 1732LC  Bronze Fixed Orifice Double Regulating Val

FEATURES & BENEFITS

• Provides precise and accurate flow regulation

• Easy to operate with handwheel and numerical indicator

• Integral orifice and test points – no need for separate DRV and metering station

• WRAS Approved for use with potable water to 85°C.

• Positive flow control at all handwheel settings

• The FODRV offers an accuracy of ± 5% on all settings, for precise flow regulation and measurement

DIMENSIONAL DRAWING

Fig. 1732, 1732M, 1732L, 1732C, 1732MC, 1732LC _ Dimensional Drawing.jpg

Fig. M2000

Stainless Steel Metering Stations

Fig. M2000  Stainless Steel Metering Stations.jpg

FEATURES & BENEFITS

• Compact, wafer design for fitting in tight spaces

• Accurate flow measurement

• Supplied with red and blue test points for upstream and downstream port identification

• Accuracy of flow measurement at normal velocities is ±5%

• WRAS Approved for drinking water applications in sizes DN65 to DN150

DIMENSIONAL DRAWING

Fig. M2000 _ Dimensional Drawing.jpg
Fig. M2000 _ Drawing.jpg

Fig. M2000

Stainless Steel Metering Stations

Fig. M2000  Stainless Steel Metering Stations.jpg

FEATURES & BENEFITS

• Compact, wafer design for fitting in tight spaces

• Accurate flow measurement

• Supplied with red and blue test points for upstream and downstream port identification

• Accuracy of flow measurement at normal velocities is ±5%

DIMENSIONAL DRAWING

Fig. M2000 _ Dimensional Drawing.jpg
Fig. M2000 _ Drawing.jpg

Fig. M3000

Stainless Steel Metering Stations

Fig. M3000  Stainless Steel Metering Stations.jpg

FEATURES & BENEFITS

• Compact, wafer design to fit between flanges

• Accurate flow measurement

• Supplied with red and blue test points for upstream and downstream port identification

• Accuracy of flow measurement at normal velocities is ±5%

DIMENSIONAL DRAWING

Fig. M3000 _ Dimensional Drawing.jpg
Fig. M3000 _ Drawing.jpg

Fig. MH733 / MHA733

Double Regulating Valve (DRV)

Fig. MH733 _ MHA733  Double Regulating Valve (DRV).jpg

FEATURES & BENEFITS

• The double regulating feature allows the valve to be used for isolation and to be re-opened to its pre-set position to maintain required flow rate

DIMENSIONAL DRAWING

Fig. MH733 _ MHA733 _ Dimensional Drawing.jpg

MH737 / MHA737

Variable Orifice Double Regulating Valve (VODRV)

MH737 _ MHA737  Variable Orifice Double Regulating Valve (VODRV).jpg

FEATURES & BENEFITS

• The double regulating feature allows the valve to be used for isolation and to be re-opened to its pre-set position to maintain required flow rate

DIMENSIONAL DRAWING

MH737 _ MHA737 _ Dimensional Drawing.jpg

Fig.MH739 / MHA739

Fixed Integral Orifice Double Regulating Valve (FODRV)

Fig.MH739 _ MHA739  Fixed Integral Orifice Double Regulating Valve (FODRV).jpg

FEATURES & BENEFITS

• Single unit Y-Pattern globe valves incorporating an integral orifice plate to form a fixed orifice flow measurement unit with regulation and isolation capacity

• The Double Regulating feature allows the valve to be used for isolation and to be reopened to its pre-set position to maintain required flow rate

• Accuracy of flow measurement is ±5% at all open positions of the valve in accordance with BS 7350: 1990

• Primarily used in injection or other circuits requiring a double regulating valve for system balancing

• External spray epoxy coated for improved durability

DIMENSIONAL DRAWING

Fig.MH739 _ MHA739 _ Dimensional Drawing.jpg

Fig. 973 & 973G

Ductile Iron with Double Regulating Feature

Fig. 973 & 973G  Ductile Iron with Double Regulating Feature.jpg

FEATURES & BENEFITS

• Robust iron body materials for long service life

• Precise flow regulation

• Fully-lugged – easy to install and operate

• Positive flow control at all settings

DIMENSIONAL DRAWING

Fig. 973 & 973G _ Dimensional Drawing.jpg

Fig. 4923 & Fig. 4923G

Butterfly Double Regulating Valves

Fig. 4923 & Fig. 4923G  Butterfly Double Regulating Valves.jpg

FEATURES & BENEFITS

• Robust, Ductile Iron valve bodies for long service life

• Stainless Steel discs as standard

• Suitable for wide temperature range -10°C to 120°C

• Fully lugged for secure installation

• Rated to PN25

• Lever and Gearbox operator options

DIMENSIONAL DRAWING

Fig. 4923 & Fig. 4923G _ Dimensional Drawing.jpg
bottom of page